Appendix
Operator's Handbook, AutroSafe Interactive Fire Alarm System, Release 3, ASAFE-FO/FE Rev. I, 2009-02-27,
Autronica Fire and Security AS
Page 123
PROLONG
DELAY
4
JKL
Available when the selected event is a
Delayed Action detection zone having
entered the fire alarm condition and is
in its T1 period. The T1 delay period
is started when a Fire Alarm signal
from a point is received.
(Not included in SOLAS version).
terminate the T1 delay period
and start the T2 delay period.
BLOCK
4
JKL
As PROLONG DELAY above.
Used in a SOLAS Action detection
zone.
The T1 delay period is started when a
Fire Alarm signal from a point is
received.
terminate the T1 delay period
and block the alarm for an
indefinite period of time.